Fire-fighting installations by height
verbatim
<18 m: hose reel + 5,000 L terrace tank + 450 LPM pump. 18–35 m: down-comer + manual alarm + 25,000 L UG tank + 900 LPM pump. MOEFA required ≥24 m. NOC needed above 18 m or 400 m² floor area (guidelines) — App-7 Reg 13 triggers at 15 m.
HP Fire NOC Guidelines Table 7
· Appendix-7 (projects over 2,500 m²) · Appendix-1 (general buildings)
| Tiers |
[{"max_h":18,"kit":"Hose reel; 5,000 L terrace tank; 450 LPM pump"},{"max_h":35,"kit":"Down-comer; manual fire alarm; 25,000 L UG tank; 900 LPM pump"}] |
| Moefa h |
24 |
| Noc h |
18 |
| Noc floor m2 |
400 |
Fire NOC
verbatim
Buildings above 15.00 m: Fire NOC from Director Fire Services required ONLY at Completion Stage; fire-safety self-declaration per HP Fire Safety Rules 2019 accompanies the application (Check List 23).
Appendix-7 (2022) Reg 16(i) · HP Fire Safety Rules 2019
· Appendix-7 (projects over 2,500 m²) · Appendix-1 (general buildings)
Fire-tender access & turning radius
verify
A 6.0 m wide hard-paved fire-tender path must reach every block, with 9.0 m turning radius at bends and head-room ≥5.0 m; gates ≥4.5 m wide.
NBC 2016 Part 4 §7 — verify
· Appendix-7 (projects over 2,500 m²)
| Path m |
6 |
| Turning radius m |
9 |
| Headroom m |
5 |
| Gate m |
4.5 |
Fire-escape staircase width
verify
Residential stair flights ≥1.5 m clear (matches App-7 Reg 13: 3.0 m total, 1.5 m per flight); riser ≤190 mm, tread ≥250 mm; handrails both sides.
NBC 2016 Part 4 Table 20 — verify
· Appendix-7 (projects over 2,500 m²)
Maximum travel distance to exit
verify
Travel distance from any point to the nearest exit ≤30 m (residential, unsprinklered) / ≤45 m if sprinklered.
NBC 2016 Part 4 Table 22 — verify
· Appendix-7 (projects over 2,500 m²)
| Max m |
30 |
| Sprinklered m |
45 |
Fire pump room & water tanks
verbatim
<18 m: hose reel + 5,000 L terrace tank + 450 LPM pump. 18–35 m: down-comer + manual alarm + 25,000 L UG tank + 900 LPM pump + pump room. MOEFA ≥24 m.
HP Fire NOC Guidelines Table 7 (verbatim)
· Appendix-7 (projects over 2,500 m²) · Appendix-1 (general buildings)
| Tiers |
[{"max_h":18,"terrace_l":5000,"ug_l":0,"pump_lpm":450,"kit":"Hose reel; 5,000 L terrace tank; 450 LPM pump"},{"max_h":35,"terrace_l":5000,"ug_l":25000,"pump_lpm":900,"kit":"Down-comer; manual alarm; 25,000 L UG tank; 900 LPM pump; pump room"}] |
| Moefa h |
24 |
Wet riser / down-comer
verify
Above 15 m: wet riser (100 mm) in each staircase with landing valves each floor; HP tiers: 18–35 m down-comer acceptable per Table 7.
HP Fire Guidelines + NBC Table 23 — verify
· Appendix-7 (projects over 2,500 m²)
Fire lift
verify
Buildings above 15 m must provide a fire lift (545 kg / 8 persons min, fireman switch, solid doors) reachable within 60 s.
NBC 2016 Part 4 §5.2 — verify
· Appendix-7 (projects over 2,500 m²)
Refuge areas
verify
Buildings above 24 m: refuge area ≥15 m² at the first floor above 24 m and every 7th floor thereafter, on an external wall.
NBC 2016 Part 4 §4.11 — verify
· Appendix-7 (projects over 2,500 m²)
| Trigger h m |
24 |
| Area m2 |
15 |
Fire command centre
verify
Buildings above 30 m require a ground-floor fire command centre with panel, PA and communication.
NBC 2016 Part 4 §4.13 — verify
· Appendix-7 (projects over 2,500 m²)
Basement / enclosed-parking smoke management
verify
Enclosed or basement parking requires mechanical smoke extraction (12 air changes/hr) and sprinklers if area >200 m².
NBC 2016 Part 4 §4.9 — verify
· Appendix-7 (projects over 2,500 m²)