Services in Himachal Pradesh

Water demand and storage, sewage treatment, waste, rainwater harvesting and the electrical rooms that go with them.

What services must the building provide?

Domestic demand 135 lpcd; storage = 1.5 days (UG tank + terrace tanks split ≈ 2:1), PLUS the fire reserve from the fire tier. IPH NOC for supply (App-7 Reg 14 verbatim).

NBC 2016 Part 9 §4 (135 lpcd) — verify — and 9 related rules below.

The rules — all 10

Water demand & storage

verify

Domestic demand 135 lpcd; storage = 1.5 days (UG tank + terrace tanks split ≈ 2:1), PLUS the fire reserve from the fire tier. IPH NOC for supply (App-7 Reg 14 verbatim).

NBC 2016 Part 9 §4 (135 lpcd) — verify · Appendix-7 (projects over 2,500 m²)
Lpcd 135
Storage days 1.5
Ug share 0.67

Sewage treatment (STP)

verify

Sewage ≈ 85% of water demand. Size the STP accordingly; if sewage >50 KLD the scheme ALSO triggers GoI Environmental Clearance (App-7 Reg 12(ii)). Treated water reused for flushing/landscape.

CPHEEO (80–85% of supply) — verify · EC trigger App-7 Reg 12(ii) verbatim · Appendix-7 (projects over 2,500 m²)
Sewage factor 0.85
Ec kld 50

Solid waste

verify

Segregated storage (wet/dry) — refuse room ≥1.1 m³ per 50 flats near the service entrance; dumper placement site reserved (App-7 Reg 22 verbatim); ground-floor garbage trolley route to the road.

SWM Rules 2016 + App-7 Reg 22 (dumper site verbatim) · Appendix-7 (projects over 2,500 m²)
M3 per 50 flats 1.1

Rain water harvesting

verbatim

Underground RWH @ 20 L/m² of roof-top area (non-drinking uses incl. fire-fighting). RWH structures allowed in setbacks below ground; community RWH permissible; NO water connection until the RWH system is operational; existing buildings must retrofit within 18 months.

Appendix-7 (2022) Reg 17 + General RWH regs (p.84) · Appendix-7 (projects over 2,500 m²) · Appendix-1 (general buildings) · Appendix-8
Litres per m2 20

Electrical: transformer, DG, rooms

verbatim

Load estimate ~3 KW/flat + common services. >50 KW → transformer space + 11 KV provision + HPSEB NOC (verbatim). Provide DG backup for lifts/common lighting (App-7 Reg 13(vi) verbatim) with a ventilated DG room outside the setback drives.

App-7 Reg 20 (verbatim >50 KW) + HPSEB practice · Appendix-7 (projects over 2,500 m²)
Kw per unit 3
Trigger kw 50

Transformer space

verbatim

If power assessment exceeds 50 KW, reserve transformer space in the layout (HPSEB verification + NOC).

Appendix-7 (2022) Reg 24 · Appendix-7 (projects over 2,500 m²)
Kw 50
Kw per unit 3

Plumbing shafts

verify

Stack bathrooms/kitchens vertically on shared shafts (0.6 × 1.2 m per pair of flats, accessible from lobbies); avoid offset stacks — every misaligned bathroom adds horizontal drainage under someone's ceiling.

NBC 2016 Part 9 practice — verify · Appendix-7 (projects over 2,500 m²)
Shaft 0.6×1.2 m

Refuse chute system

verbatim

A refuse chute system for domestic solid waste is MANDATORY for buildings exceeding 5 storeys.

Appendix-7 (2022) Reg 19 · Appendix-7 (projects over 2,500 m²)
Storeys 5

Service & maintenance access

verify

Terrace access to all roofs, ladder access to tanks, valve chambers on the drive, STP with truck access for desludging, meter room at ground level.

Design practice — verify · Appendix-7 (projects over 2,500 m²)

Infrastructure: street lights, ducts, water reservoir

verbatim

Street-light poles every 30.00 m on either side of roads; service ducts along roads; community water reservoir; dumper site reserved.

Appendix-7 (2022) Reg 25 · Appendix-7 (projects over 2,500 m²)
Light spacing m 30
5 of these 10 were encoded from secondary sources rather than read off the gazetted text — they carry a “verify” tag above. The engine applies them and the substance is believed correct, but confirm the exact figure against the notification before you build to it.
Worked example — a 500 m² plot on a 9 m road

Computed live by the same engine that produces the drawings — not a stored example.

9 m road 2 m rear 3 m front 2 2 319 m²

Drawn square for clarity. A real tatima is not square — that is what the tracer is for.

RegimeAppendix-1 (General Building)
FAR1.75
Setbacks (F / R / sides) 3 / 2 / 2 m
Buildable footprint319 m²
Height cap21 m
Storeys3
Permissible built-up 875 m²
Parking required9 ECS

500 m² × FAR 1.75 = 875 m² permitted. The 319 m² footprint over 3 storeys could hold 956 m², so FAR is the binding constraint — the height allowance is not fully usable here.

Sources on this page
  • NBC 2016 Part 9 §4 (135 lpcd) — verify
  • CPHEEO (80–85% of supply) — verify · EC trigger App-7 Reg 12(ii) verbatim
  • SWM Rules 2016 + App-7 Reg 22 (dumper site verbatim)
  • Appendix-7 (2022) Reg 17 + General RWH regs (p.84)
  • App-7 Reg 20 (verbatim >50 KW) + HPSEB practice
  • Appendix-7 (2022) Reg 24
  • NBC 2016 Part 9 practice — verify
  • Appendix-7 (2022) Reg 19
  • Design practice — verify
  • Appendix-7 (2022) Reg 25

Official text: HP Town and Country Planning Rules, 2014 ↗

Spotted something wrong?

Rules change and we would rather hear it from you than have somebody build to a stale number. No account needed.

Does your plot comply?

Trace your tatima and these 10 rules — and the 70 others — are checked against your actual boundary, with the number behind each verdict.

Check my plot → All Himachal Pradesh rules →
Ask AI

Nothing matched in the rulebook — try other words (parking, height, fire, setback, water…).

looking it up…

Answers come straight from the building rules for 12 states we cover, plus the glossary and calculators — each with its citation.